Automatic Management System for Maoming Tank Farm

Automatic Management System for Maoming Tank Farm

Overview on IndustrialIT SCADA VantageTM

Solution of ABB SCADA system is IndustrialIT SCADA VantageTM that is based on operation system Windows XP and jointly developed with world famous petroleum company, and has been confirmed

to be successful in actual operation. The database of the system can perform memory-resident operation. With the help of data compression and database fault-tolerance technique, the database of the system can perform online configuration and modification.SQL was used

as development tool of high level application. With the help of Visual Basic technology extended human-computer interface can be developed easily. VB data environment can be widely used in tendency display, alarm/incident display, dynamic map, dynamic data and dynamic sign. There are many ways, such as OPC, DDE, ODBC, OLEDB and SQL, via which interconnection between different systems can be realized. It also supports time stamp.

The server SCADA system adopt redundant and hierarchy structure, which makes main server becomes field-server’s redundant equipment and vice versa. It supports multi communication protocol and multi path control devices, can perform data interchange

with all kinds of control unit, RTU and DCS equipment. It also can perform automatic switch on communication link

IndustrialIT SCADA VantageTM system adopt international communication standard IEC6870-5-104 to perform communication with other control center. This means that the SCADA system provided by ABB can be used by dispatching center of general headquarters.

IEC6870-5-104 is an optimized data-interchange product that is developed basing on WAN and MMS and provide industrialized information service.

According to rules and regulation, communication protocol IEC6870-5-104 provides multi

management capabilities. Both client and server within the system boast these capabilities.

IndustrialIT SCADA VantageTM system can provide following transactions that are occurred between dispatching centers

It can exchange different type of data, such as SCADA data, watt consumption or even exchange progress sheet.

Periodically transfer data set that represents request or starting of incident and with time stamp

Supporting customization- define data information

SCADA Vantage main computer receive real-time data created by field equipment, save them as history data via an interface. The two factors that we concern about database is data collection cycle and storage volume. Both real-time data and history data can be reproduced through tendency diagram. Data is saved in the form of database. Database adopt client/server distributed and open framework.

Report form 1.1.2 Report form production and distribution

You can directly read report form on the computer, it also can be emailed or copied.

With the help of SQL,ODBC AND DDE, as well as Microsoft hierarchy structure and menu,

you can visit and use history data and real-time data. Basing on technical specification

and real-time data produced by equipment, report form containing incident information also can be produced. The style of these reports can adopt that of engineering report or finance and accounting report.

Monitoring, control and tendency

Basing on the special structure and function of SCADA Vantage system, the main computer of SCADA Vantage system may perform monitor and control function at the very station.

Refreshing frequency on data monitor and control will depend on the situation of communication line. The data to be displayed include dynamic data and fly-over data.

Data refreshing frequency depends on the real situation of communication system. SCADA Vantage boasts rapid scanning capability. Any measurement point among the whole can be browsed via tendency diagram. It also boasts key area browsing, zoom in and zoom out function

the number of clients

In fact, there is no limit on the number of clients for SCADA Vantage system. A small bandwidth is required for client communication, which almost suit any customers, including both local customers and remote customers. Customer can visit system through LAN, WAN, modem, any kinds of communication method within VPN. Client may locate at the field, or any other places. During implementation period, ABB can provide customer with service and help.

The capability of SCADA system

The SCADA Vantage system of ABB supports the recording of SMSCS real-time data, state, alarm, history trend, journal on alarm and incident, which is saved in the database of system server and can be read. Database possesses self-maintenance and automatic timing copy function.

collection of alarm message.

SCADA Vantage display unanswered alarm list on the lower right corner of a standard screen. SCADA system also adopts main screen map display method. You can open a picture

by press a page button in which alarm message collection is included. SCADA Vantage

will arrange the order of alarm message per priority and time sequencing. When alarm

occurs to one of the alarm collection, the relevant light among the alarm collection will flash until it has been responded. When there is alarm being neglected, an aural signal may be produced by SCADA Vantage to warn the operator. The selection of sound style will depend on your company’s preference. Response to any alarm can be done by placing the cursor on the alarm point and double click mouse. You can rearrange the order of alarms within the alarm collection by click the item within the title bar.

Collection of operator alarm

 

Operator alarm is a type of single or repeated alarm that can be set by operator. This

type of alarm can contain information defined by customer. Operator alarm is similar to an alarm clock, which means alarm appears in special time span and with special information. You can open a picture relating to this type of alarm by click relevant command button.

Click “ ”button to increase new operator alarm. New operator alarm dialog box will appear in front of you, as shown below:

Enter operator alarm title and click button, a new page relating to features and configuration of operator alarm will appear, as shown below:

You can also open this page by clicking relevant alarm in operator alarm sheet. In this page, you can obtain information such as description on operator alarm, comments, schedule type and re-schedule type. Activation of alignment of activity means daily starting time

for an alarm assigned to a designated activity. Activation interval is effective only when

timing style is defined as Interval or Interval offset. Activation interval is defined as the time span from activation of an alarm to alarm signal being sent out by the alarm device. Operator alarm feature is used for defining alarm zone and priority. Operator alarm zone and priority can be determined by clicking one of options appeared on the screen. Operator alarm information is described as displayed information when an alarm really occurs.

Features of tendency chart

Although all real-time system and SCADA system boast tendency chart function, SCADA Vantage system has obvious advantage over other systems.

Trend diagram basing on real-time data can be saved, whatever ways used by you to visit it.

The automatic online archiving and reappearing function for blocks of tendency chart

allow customer visit data tendency chart representing a long time.

1.1.6 Application management system for customer station(CAM)

This software is responsible for the management of client station upgrading.

When the client stations of SCADA Vantage system are connected with server, CAM

Will check software of each client to identify whether it is the newest version.

It will perform automatic upgrading in case that the software is not the newest version.

In case that software upgrading is needed for client, CAM can download necessary component to client station and perform upgrading. Allowing system administrator save new software inside CAM and automatic upgrading client station make software upgrading easier. At the same time, problems stemmed from upgrading can be reduced.

Flexible framework

SCADA Vantage system can select any operation mode from following:

Single computer system without redundant function

Redundant system which can perform automatic switch in case of malfunction and

possess warm standby function.

Hierarchy server and point to point, peer to peer server

Automatic

Visit via internet

Single computer system is mainly applied in middle and small system. Short time rest is allowed for this type of system.

Redundant system with warm standby function is applied in main control center where

operating condition is very strict. Rest is not allowed for system in main control center.

Hierarchy server is applied where database is located at different fields, so as to minimize influence stemmed from out of service of computer. But there must be

a real-time host database for use of inquiry and visit. The upgrading of host database

is done via field database.

Point to point server is used for off-line warm backup. Compared with host server, off-line server is placed at different place or places far away and frequency of data refreshing is very low. Once system at main control center is taken out of service

by catastrophe, off-line backup system will take over

Real-time database and history database can be visited by table.

Human Machine Interface(HMI)

IndustrialIT SCADAVantage is applied as HMI monitoring software and used by SCADA system. It is used for equipment control, monitoring process data, display of data/state/alarm, recording of alarm/incident, production of report form, and so on.

Operator station receives data from SCADA system server without interrupt and presents them to local HMI to finish command and data input at local station level. With it you can provide local station CRT with graph and form and obtain data, alarm message

,record, graph, real-time tendency line, history tendency line as well as history data.

The application of history tendency can provide each recorded variable with selectable sample cycle, dead zone and time cycle.

IndustrialIT SCADAVantage:

The picture style provided by IndustrialIT SCADAVantage include:

Provide local SCS with operation interface. Provide each unit in local station with

graph or table display function. With a series of graph and table display, as well as printed incident record and report, the operator can secure status messages on station and unit in the station through color(CRT display) and value.

Picture selection is done through menu selection, and with one touch you can switch from one picture to another one. The initial picture will display panorama of station and field, including main equipment and buildings. Each picture at lower level will

display a smaller area of the field and provide more detailed process information compared with that contained in the last one.

With the aid of keyboard and mouse, operator can modify operation parameter of a station, turn off one pump unit, switch on/off valves, change set-point for a station, change alarm threshold value and change station operation mode.

There is dynamic zone in the picture that is reserved for inputting data and command.

Operator can input relevant data and command in this zone to change system parameter, turn on/turn off pump unit and change operation mode. When a new picture is selected,

the way for data entry is not selected automatically. At first, place cursor at place where data to be entered (by the time, the zone will be lightened). Then, you can input desired data or select command or data from dialog box. At last, you can click

acceptbutton in the picture ( or press return key) to receive new data or command.

In case that what is inputted has not been accepted in designated time, the command or data will be restored. It can accept various data, including transfinite testing data and preference upgrading data. System will not accept new data or command until

Return key or accept button is pressed. Data or command inputted can be edited before being accepted. At the same time, any inputted data or command will be saved in alarm/incident printer and which is displayed in alarm/incident collection picture.

The style and type of pictures to be displayed include:

· panoramic display

· form display

· measurement chart display

· measurement table display

· Chart display for pump unit

· Table display for pump unit

· Operating curve display for pump unit

· Set point display

· parameter display for control loop

· parameter maintenance display

· real-time tendency display

· history tendency display

· communication status display

· alarm collection display

· display on history of alarm/incident

· record on alarm/incident

· display on report form

· display on hourly report

· display on daily report

Description on control system configuration

1) system configuration in central control room

Equipment equipped in the central control room includes: a set of redundant SCADA system server, a set of WEB server, a set of MIS server, an engineer station and 4 operator stations, each of them is also equipped with SCADA system database software, engineer software/operator software and interface software for management of plant network.

Configuration for systems in instrument cabinet room and instrument cabinet room in control center.

Equipment equipped in cabinet room of control center includes: a pair of redundant AC800M PM861 controller used in DCS control station, a few S800 I/O card used in local and distant I/O station.

The equipment equipped in instrument cabinet room includes two pairs of redundant AC800M PM861 controller used in DCS control station, a few S800 I/O card used in local and distant I/O station, a operator station (also used as engineer station)

AC800M controller

Characteristic for controller provided by Beijing Master Automatic Control Engineering Co., Ltd:

Controller: including CPU, communication module, power module and various accessories. There are a number of types of controller module available for selection, which is different from each other in terms of process capapacity, size of memory and redundant supporting.

Each controller module is equipped with two Ethernet ports, which is used for communication with other controllers, and interactive with operator, engineers and managers. For situation where the top priority is reliability it is recommended that these two ports can be equipped as redundant ports.

In addition, RS-232C port should be involved to perform point to point communication between CPU and programming/debugging tool, the third side system and equipment.

Actual parameter for AC800M controller which is used in this project:

CPU: 32 bits processor, with 133MHz/48MHz as clock frequency.

RAM: 16/32/64MB (SD-RAM), with standby battery, which is used for program storage, can be equipped with 8MB flash card.

Supporting following interfaces:

Ethernet port:2, Ethernet (IEE 802.3) communication interface with 100M/s as transmission rate, RJ-45 interface, supporting redundant configuration.

RS232C interface: 2

Switching time for redundant controller: maximum: 10ms,3-7ms in general

Switching time for redundant network: 1 second

Clock synchronization time: according to CNCP agreement, synchronization time between controllers is 1ms.

Power supply: 24VDC, meet IEC 61131-2 standard

Environmental temperature:-25℃ to 70℃, forced cooling can be saved.

Rail installation, flexible and compact modular structure

Protection class: IP20, meet EN 60529 and IEC 529

Supporting replacing without cutting of power

Supporting redundant power supply

TCP/IP can be applied for communication between AC800 controllers of different systems.

One controller can be connected with 8 S800IO stations, each of which can have 12 I/O modules. The total I/O modules amount to 96.

If connected with ProfibusDP/DPV1, one controller can be connected with 79 stations at the most, each station can have 24 I/O modules, the total modules amount to 79x24

S800 process I/O station

Following S800 I/O module will be chosen by DCS system in cabinet room of control center:

Analog input module: AI815, HART 0-20mA, 1-5VDC, 8 channels.

Digital input module: DI 810, 24VDC, 16 channels.

Digital output module: DO810, 24VDC, 16 channels.

Following S800 I/O module is chosen by DCS system between instrument

Analog input module: AI810, 0-20mA, 1-5VDC, 8 channels.

Analog output module: AO810, 0-20mA, 1-5VDC, 8 channels;

Analog input module: AI830,RTD,Pt100, 8 channels;

Analog input module: AI815, HART 0-20mA,1-5VDC, 8 channels;

Digital input module: DI810,24VDC,16 channels;

Digital output module: DO810,24VDC, 16 channels.